New York regulations

9 NYCRR 1504.7

Executive Department

Browse New York regulations by title, part, and section.

Local water-flow alarm

Local water-flow alarm

Compiled text through Sep 15, 2021

Register checked through Jul 29, 2026

No later Register activity identified in this check.

Dates and status
Compiling agency
Executive Department
Text status
Source receipt
Compiled text through
Sep 15, 2021
Register checked through
July 29, 2026/Vol. XLVIII, Issue 30 (2026-07-29)
Activity status
No later Register activity identified in this check.
Source snapshot
Jun 6, 2026
(a)A local water-flow alarm shall be installed in new sprinkler systems that are used to protect a public hall or stairs or a required means of egress, or for systems where a new sprinkler pipe supplies more than five sprinkler heads, or for other systems where deemed necessary by the department.
(b)Required local water-flow alarms shall include sounding devices of sufficient size and so located that the sound can be heard by the occupants or by an authorized person on duty at all times to take proper action. The alarm shall be caused to sound when the flow of water through any portion of the sprinkler piping is equal to or greater than that flowing from a single sprinkler head.

State Register activity

No Register activity identified in this check.Register checked through July 29, 2026/Vol. XLVIII, Issue 30 (2026-07-29).

LawEngine organizes New York regulations for fast review. Use independent legal judgment before filing.