9 NYCRR 1501.4

Executive Department

Browse New York regulations by title, part, and section.

Operating temperatures

Operating temperatures

Compiled text through Sep 15, 2021

Register checked through Jul 29, 2026

No later Register activity identified in this check.

Dates and status
Compiling agency
Executive Department
Text status
Source receipt
Compiled text through
Sep 15, 2021
Register checked through
July 29, 2026/Vol. XLVIII, Issue 30 (2026-07-29)
Activity status
No later Register activity identified in this check.
Source snapshot
Jun 6, 2026
(a)Fire detecting devices of the fixed temperature type shall operate when the temperature rises to 165 degrees Fahrenheit, when installed in areas where the maximum temperature at the ceiling is 100 degrees Fahrenheit. Where higher temperatures normally exist at the ceiling, such as in furnaces or boiler rooms, kitchens, laundries, etc., fire detecting devices may operate at higher temperatures providing such higher operating temperatures are commensurate with the ceiling temperatures.
(b)Fire detecting devices of the rate-of-rise type shall operate whenever the rate of the rise in temperature exceeds 20 degrees per minute.