Sounding devices
Compiled text through Sep 15, 2021
Register checked through Jul 29, 2026
No later Register activity identified in this check.
Dates and status
- Compiling agency
- Executive Department
- Text status
- Source receipt
- Compiled text through
- Sep 15, 2021
- Register checked through
- July 29, 2026/Vol. XLVIII, Issue 30 (2026-07-29)
- Activity status
- No later Register activity identified in this check.
- Source snapshot
- Jun 6, 2026
(a)New sounding devices within a hotel or similar dwelling shall be of the same type and shall sound a clear audible signal that is distinct from all signals by other sounding devices used in the vicinity.
(b)New sounding devices shall be located approximately eight feet above floor level wherever practicable.
(c)New fire alarm systems shall have no more than 14 sounding devices connected on a single direct current circuit, nor more than 10 sounding devices connected on a single alternating current circuit.